High Frequency UPS 1
Online high frequency single phase three phase UPS power supply for industrial equipment Main Features · Double conversi
Description
Basic Info.
Model NO. | DPH |
Standby UPS | Sine Wave Output UPS |
Output Capacity | Small Type |
Equipment Mode | Centralized Model |
Brand | Daopulse/OEM/ODM |
Input Frequency Range | 40~70Hz |
Line-Bat Transfer | 0ms |
Noise Level | Less Than 50 dB |
Transport Package | Standard Export Packing |
Specification | 421*190*318mm |
Trademark | Daopulse |
Origin | Guangzhou, China-Mainland |
HS Code | 8504402000 |
Production Capacity | 500000 Pieces/Year |
Product Description
Online high frequency single phase three phase UPS power supply for industrial equipmentMain Features
· Double conversion topology technology, pure sine wave output.· Advanced DSP digital control technology.· Environmental Friendly and energy saving, as the input power factor is up to 0.99.· Wide input voltage and frequency range, 110 -- 240Vac, 40 -- 70 Hz.· 0ms Line-Bat transfer , ensure the safety and reliablity of load. · ECO mode optional, reduce the UPS power consumption. · Low audible noise (below 50 dB), will not affect your daily life.
Specfictations
Model | 1K | 2K | 3K | 6K | 10K |
Phase | Single phase with ground | ||||
Input | |||||
Rate capacity | 1KVA/900W | 2KVA/1.8KW | 3KVA/2.7KW | 6KVA/6KW | 10KVA/10KW |
Rate voltage | 110/115/120/127VAC or 220/230/240VAC | 220/230/240VAC | |||
Turn on voltage range | 55-150VAC or 110-300VAC ≤50% load | 110-300VAC ≤50% load | |||
80-150VAC or 160-300VAC ≤100% load | 176-300VAC ≤100% load | ||||
Frequency range | 40~70Hz | 46~54Hz or 56~64Hz | |||
Power factor | ≥0.99 100% load | ||||
THDI | ≤5% | ≤4% | |||
Output | |||||
Rate voltage | 110/115/120/127VAC or 220/230/240VAC | 220/230/240VAC | |||
Voltage regulation | ±1% | ||||
Line mode frequency | 47~53Hz or 57~63Hz | 46~54Hz or 56~64Hz | |||
Bat mode frequency | 50Hz or 60Hz ±0.1Hz | ||||
Voltage harmonic | ≤2% R load | ≤1% R load | |||
≤4% RCD load | ≤4% RCD load | ||||
Crest ration | 3:1 | ||||
Line-Bat transfer | 0ms | ||||
INV-Bypass transfer | ≤4ms | 0ms | |||
Over load | 100%±5%<load≤110%±5%:10min;110%±5%< load ≤130%±5%:1min;load>130%±5%:1s; ( transfer to bypass and alarm) Note: 6-10K line mode | ||||
Efficiency | |||||
Line mode | > 90% | > 91% | > 91% | > 94% | > 94% |
Bat mode | > 89% | > 89% | > 90% | > 91% | > 91% |
Bat | |||||
Number | 3 | 6 | 8 | 16 or 20(20 only long) | |
Charger voltage | 41.0VDC | 82.1VDC | 109.6VDC | 218.4VDC/273VDC | |
Charge current (stand) | 1.5A | 1.2A | 1A | ||
Charge current(long) | 1A/2A/4A/6A/8A(adjustable) | 4.0A | |||
Size and weight | |||||
Stand UPS(mm) | 397*145*220 | 421*190*318 | 421*190*318 | 369*190*688/ | 442*190*688 |
Weight(kg) | 12 | 22.5 | 32.2 | 54 | 66 |
Long time UPS(mm) | 397*145*220 | 421*190*318 | 369*190*318 | 442*190*318 | |
Weight(kg) | 6.3 | 10.5 | 11.7 | 13 | 16 |
Environment | |||||
Work temperature | 0ºC~40ºC | ||||
Work humidity | 20%~95% | ||||
Audible noise | ≤50dB | ≤55dB | ≤58dB | ||
Communication | RS-232/USB/SNMP card adjustable |
Our Contact
Send now